Technical Data Sheet
2/13/2015
Model: RKA5480YXG (TRK5480Y)
Product Description
Type: Rotary
Application: HBP/AC - Air Conditioning
Refrigerant: R-134a
Voltage/Frequency: 460V 3~ 60Hz 380-420V 3~
50Hz
Version: N/A
Product Specifications
Performance
Refrigeration Capacity Input Power Efficiency
Condition Test Voltage Btu/h kcal/h W W Btu/Wh kcal/Wh W/W
EVAP TEMP COND
TEMP
AMBIENT
TEMP
RETURN
GAS
LIQUID
TEMP
EN12900
ASERCOM
460V 3~
60HZ
7549 1902 2212 766 9.86 2.48 2.89 5°C (41°F) 50°C (122°F) 32°C (90°F) 15°C (59°F) 50°C (122°F)
EN12900
ASERCOM
400V 3~
50HZ
6171 1555 1808 655 9.42 2.37 2.76 5°C (41°F) 50°C (122°F) 32°C (90°F) 15°C (59°F) 50°C (122°F)
General
Evaporating Temp. Range: -15°C to 15°C (5°F to 59°F)
Motor Torque: Low Start Torque (LST)
Compressor Cooling: Fan
Mechanical
Weight: 11
Weight Unit of Measure: KG
Displacement (cc): 18.1
Oil Type: Polyvinylether
Viscosity (cSt): 68
Oil Charge (cc): 414
Electrical
Voltage Range (50 Hz): 342-462
Voltage Range (60 Hz): 396-506
Locked Rotor Amps (LRA): 16
Rated Load Amps (RLA 50 Hz): 2
Rated Load Amps (RLA 60 Hz): 2
Max. Continuous Current (MCC in Amps): 3.8
Motor Resistance (Ohm) - Main: 13.5
Motor Resistance (Ohm) - Start: 13.5
Motor Type: 3PH
Overload Type: N/A
Relay Type: N/A
Agency Approval
Komentáře k této Příručce