L:\~ Andreea temp\ZZ Low Temp Scroll Datasheets\WORD_datasheets\Outdoor units\VSAG515ZXTHM_preliminary.doc 14/10/2011
Unit BOM 32L3642-2E
Fan Motor 810S186B40 Adjustable Fan Ctrl (A) LAFC-001
Unit MODEL
SAG515ZXTHM
Fan Motor Qty 2
Fan Motor RLA 1.9 Defrost Timer (Tn) LTCG-T2
Refrigeration RANGE -40°F to 10°F Fan Blade 51528-3
Design Pressure Low 181 Fan Guard 70832
Design Pressure High 450 Shroud 70611-1 Receiver Heater (R) LHR-223
Volts - HZ - Ph 200-230V 3~ 60HZ
Voltage Range 180 - 253 High Pressure switch 84095-2L Solenoid Valve (S) KSVC-285
Min. Circuit Ampacity 16.49 Low Pressure Control 84026-2
Max. Fuse Size 25 Dual Pressure Conrol Disconnect (D) KDSG-301
Compressor MODEL VSAG513ZXT Condenser 50785-4
Compressor BOM VS123RT-008-A4 Head Master Valve 70083
Compressor LRA 80 Check Valve 56626
Compressor RL
9.98 Process Valve
Liquid Valve
OverLoad INTERNAL Suction Valve 31529-2
32xYYYY- 2ERA(F)TnDS
Relay E Enclosure
Run Capacitor Receiver 51084 R Receiver Heater
Run Capacitor Rating Receiver Qty 1 A Adjustable fan control
Start Capacitor Accumulator TK00042000 F Fixed fan Control
Start Capacitor Rating Liquid Filter 52000-164D T1 Defrost timer option
Contactor 91014B Sight Glass 70084-2 T2 Defrost timer & Defrost Heaters Contactor
Suction Filter 70822-5S D Disconnect
Unit Drawing DGU1950-L303 S Solenoid liquid Valve (supplied loose)
Wiring no Fan controls WD23-2XT2L CrankCase Heater 14947869
BOM INDEX DESCRIPTION
Parts/Specifications
STANDARD OPTIONAL
WD23-2XT2L
REVISION
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD
PROTECTOR. ALLOW TIME FOR RESET.
USE COPPER CONDUCTORS ONLY.
(EMPLOYER DES CONDUCTEUERS DE CUIVER
SEULEMENT.)
DEFROST
HEATERS
CONTACTOR COIL
FAN 2
L1
CRANK CASE
HEATER
COMPRESSOR
TERMINAL
C
S
R
GRD
L1 T1
RED
YELLOW
BLACK
COMPRESSOR
CONTACTOR
T1
L1
T2
L2
COMPRESSOR CONTACTOR
NC AUXILIARY SWITCH
L3
L2
T3
T2
COMPRESSOR
CONTACTOR COIL
see note A
P1
HP LP
DEFROST
HEATERS
CONTACTOR
T3
L3
T1
L1
T2
L2
T3
L3
L2
L3 T3T1 F1 F2
1
3
DEFROST CONTROL
RANCO 8145-xx
PRECISION 6145-xx
N
2
4
X
IMPORTANT:
FAN 1
CONDENSING UNIT WIRING, 230V 60Hz 3 Ph,
Liquid Injection Solenoid,
Fan control,
T1 & T2 defrost options
GENERAL NOTES:
A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN
PANEL AS SHOWN
B. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR.
ALLOW TIME FOR RESET.
FACTORY COMPONENTS
OPTIONAL FIELD COMPONENTS
OPTIONAL FACTORY COMPONENTS
HP
LP
FC
FAN CONTROL
LOW PRESSURE CONTROL
HIGH PRESSURE SWITCH
FIELD WIRING NOTES
1. ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL
APPLICABLE LOCAL AND NATIONAL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY
TO L1, L2, AND L3 IN COMPRESSOR CONTACTOR OR TO L1, L2 AND L3 IN
DISCONNECT SWITCH (IF PROVIDED). USE COOPER CONDUCTORS
ONLY. (EMPLOYER DES CONDUCTEURS DE CUIVER SEULEMENT.)
PROVIDE EQUIPMENT GROUNDING CONDUCTOR.
USE 75°C (MIN.) WIRING
3. DEFROST HEATERS LOADS SHOULD NOT BE HIGHER THEN THE
MAXIMUM HEATERS LOAD INDICATED ON THE UNIT LABEL.
DEFROST HEATERS TO BE CONTROLLED WITH A CONTACTOR AS SHOWN
ON THE DIAGRAM.
NOTES
DT
SOLENOID
LIQUID INJECTION
COMPRESSOR CONTACTOR
NO AUXILIARY SWITCH
DISCHARGE LINE THERMOSTAT
DT
POWER SUPPLY
208-230 / 60 / 3
RECEIVER
HEATER
TERMINAL
BOARD
THERMOSTAT
REL
MAR. 11, 2011
VSAG515ZXTHM
TPC___preliminary
October 14, 2011
Komentáře k této Příručce